| IBM UNIX服务器全系列常用数据一览表 |
|
| 2006-03-05 00:25:22 作者:官方 来自:http://www-900.ibm.com |
| |
|
尺寸 (mm) |
功率 (kVA) |
| 机型 |
宽 |
深 |
高 |
输入功率 |
| |
|
|
|
标配 |
满配 |
| 7043-150 |
420 |
460 |
165 |
2 |
4 |
| 7044-170 |
200 |
515 |
490 |
0.4 |
0.6 |
| 7044-270 (有机架) |
340 |
713 |
610 |
0.3 |
0.47 |
| 7044-270 (无机架) |
222 |
713 |
600 |
0.3 |
0.47 |
| 7046-B50 |
447 |
612.1~751.8 |
88 |
0.12 |
0.147 |
| 7026-B80 |
482 |
617 |
217 |
0.29 |
0.46 |
| 7025-F50 (有机架) |
350 |
745 |
620 |
0.47 |
0.68 |
| 7025-F50 (无机架) |
245 |
695 |
620 |
0.47 |
0.68 |
| 7025-F80 |
483 |
728 |
610 |
0.59 |
0.86 |
| 7026-H70 |
443 |
870 |
350 |
0.46 |
0.75 |
| 7026-H80 CEC柜 |
445 |
820 |
218 |
0.32 |
0.48 |
| 7026-H80 I/O柜 |
445 |
820 |
218 |
0.23 |
0.54 |
| 7026-M80 CEC柜 |
445 |
826 |
356 |
0.39 |
0.6 |
| 7026-M80 I/O柜 |
445 |
820 |
218 |
0.23 |
0.54 |
| 7017-S7A CEC柜 |
567 |
1041 |
1577 |
- |
1.887 |
| 7017-S7A I/O柜 |
650 |
1019 |
1577 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S7A I/O单元 |
443 |
843 |
440 |
0.5 |
0.65 |
| 7017-S80 CEC柜 |
567 |
1041 |
1577 |
2.129 |
- |
| 7017-S80 I/O柜 32U |
650 |
1019 |
1577 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S80 I/O柜 36U |
644 (有侧板) |
1098 (前后门) |
1804 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S80 I/O柜 36U |
623 (无侧板) |
1042 (无前门) |
1926(-48伏直流电源) |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S80 I/O柜 42U |
644 (有侧板) |
1098 (前后门) |
2015 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S80 I/O柜 42U |
623 (无侧板) |
1042 (无前门) |
2015 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S80 I/O单元 |
443 |
843 |
440 |
0.4 |
1 |
| 7017-S85 CEC柜 |
565 |
1201 |
1577 |
2.129 |
- |
| 7017-S85 I/O柜 36U |
644 (有侧板) |
1147 (前后门) |
1804 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S85 I/O柜 36U |
623 (无侧板) |
1042 (无前门) |
1926(-48伏直流电源) |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S85 I/O柜 42U |
644 (有侧板) |
1147 (前后门) |
2015 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S85 I/O柜 42U |
623 (无侧板) |
1042 (无前门) |
2015 |
4.8(1PDU) |
14.4(3PDU) |
| 7017-S85 I/O单元 |
443 |
843 |
440 |
0.4 |
1 |
| POWER3 高节点 |
560 |
1016 |
356 |
- |
- |
POWER3 I/O 扩展单元
|
280 |
813 |
160 |
- |
- |
| SP frame 500 |
711 |
1015 |
1245 |
- |
4.2 |
| SP frame 550 |
922 |
1295 |
1925 |
- |
8.1 |
| 7014-S00 RACK |
650 |
1019 |
1578 |
4.8(1PDU) |
14.4(3PDU) |
| 7014-T00 RACK |
644 (有侧板) |
1098(前后门) |
1804 |
4.8(1PDU) |
19.2(4PDU) |
| 7014-T00 RACK |
623 (无侧板) |
1042 (无前门) |
1926(-48伏直流电源) |
4.8(1PDU) |
19.2(4PDU) |
| 7014-T42 RACK |
644 (有侧板) |
1147 (前后门) |
2015 |
4.8(1PDU) |
19.2(4PDU) |
| 7014-T42 RACK |
623 (无侧板) |
1042 (无前门) |
2015 |
4.8(1PDU) |
19.2(4PDU) |
| |
功率(kVA) |
重量 (kg) |
TPC-C |
| 机型 |
输出功率 |
最小配置 |
满配 |
tpmC |
$ /tpmC |
| |
标配 |
满配 |
|
|
|
|
| 7043-150 |
0.15 |
0.23 |
14.5(标配) |
18 |
- |
- |
| 7044-170 |
- |
- |
17.7 (标配) |
20.4 |
- |
- |
| 7044-270 (有机架) |
0.297 |
0.245 |
37 |
45 |
- |
- |
| 7044-270 (无机架) |
0.297 |
0.245 |
37 |
45 |
- |
- |
| 7046-B50 |
0.12 |
0.14 |
14.5 (标配) |
- |
- |
- |
| 7026-B80 |
- |
- |
37.5 |
45 |
- |
- |
| 7025-F50 (有机架) |
0.425 |
0.61 |
35 |
55 |
9853.13 |
65 (4-way) |
| 7025-F50 (无机架) |
0.425 |
0.61 |
35 |
55 |
9853.13 |
65 (4-way) |
| 7025-F80 |
0.56 |
0.84 |
70 |
95 |
33571.39 |
58.94 (6-way) |
| 7026-H70 |
0.455 |
0.75 |
74.1 |
88.6 |
17133.73 |
78.50 (4-way) |
| 7026-H80 CEC柜 |
0.3 |
0.45 |
41 |
52 |
17133.73 |
78.50 (4-way) |
| 7026-H80 I/O柜 |
0.22 |
0.515 |
41 |
52 |
- |
- |
| 7026-M80 CEC柜 |
0.37 |
0.55 |
59.7 |
- |
66750.27 |
45.46 (8-way) |
| 7026-M80 I/O柜 |
0.22 |
0.515 |
41 |
52 |
- |
- |
| 7017-S7A CEC柜 |
- |
1.774 |
400 (标配) |
- |
- |
- |
| 7017-S7A I/O柜 |
- |
- |
130 (空) |
- |
- |
- |
| 7017-S7A I/O单元 |
0.5 |
0.65 |
81.4 |
93.2 |
- |
- |
| 7017-S80 CEC柜 |
- |
2.023 |
400 (标配) |
- |
135815.7 |
52.7 (24-way) |
| 7017-S80 I/O柜 32U |
- |
- |
159 (空) |
- |
- |
- |
| 7017-S80 I/O柜 36U |
- |
- |
244 (空) |
- |
- |
- |
| 7017-S80 I/O柜 36U |
- |
- |
244 (空) |
- |
- |
- |
| 7017-S80 I/O柜 42U |
- |
- |
261 (空) |
- |
- |
- |
| 7017-S80 I/O柜 42U |
- |
- |
261 (空) |
- |
- |
- |
| 7017-S80 I/O单元 |
0.36 |
0.9 |
81.4 |
93.2 |
- |
- |
| 7017-S85 CEC柜 |
- |
2.023 |
- |
- |
220807.27 |
43.3 (24-way) |
| 7017-S85 I/O柜 36U |
- |
- |
244 (空) |
- |
- |
- |
| 7017-S85 I/O柜 36U |
- |
- |
244 (空) |
- |
- |
- |
| 7017-S85 I/O柜 42U |
- |
- |
261 (空) |
- |
- |
- |
| 7017-S85 I/O柜 42U |
- |
- |
261 (空) |
- |
- |
- |
| 7017-S85 I/O单元 |
0.36 |
0.9 |
81.4 |
93.2 |
- |
- |
| POWER3 高节点 |
- |
- |
108 |
137 |
- |
- |
| POWER3 I/O 扩展单元 |
- |
- |
18 |
28 |
- |
- |
| SP frame 500 |
- |
5 |
232 |
414 |
- |
- |
| SP frame 550 |
- |
10.5 |
441 |
984 |
- |
- |
| 7014-S00 RACK |
- |
- |
130 (空) |
- |
- |
- |
| 7014-T00 RACK |
- |
- |
244 (空) |
- |
- |
- |
| 7014-T00 RACK |
- |
- |
244 (空) |
- |
- |
- |
| 7014-T42 RACK |
- |
- |
261 (空) |
- |
- |
- |
| 7014-T42 RACK |
- |
- |
261 (空) |
- |
- |
- |
注:在选择UPS时,请参考输入功率。
原文链接:http://www-900.ibm.com/cn/support/viewdoc/detail?DocId=1611050000003
|
| 发表评论 | 查看评论
|
| |
|
|
|